Extensive Definition
portal Energy Electric
power transmission, a process in the delivery of electricity to consumers, is
the bulk transfer of electrical power. Typically, power
transmission is between the power plant
and a substation
near a populated area. Electricity
distribution is the delivery from the substation to the
consumers. Electric power transmission allows distant energy
sources (such as hydroelectric power
plants) to be connected to consumers in population centers, and may
allow exploitation of low-grade fuel resources that would otherwise
be too costly to transport to generating facilities.
Due to the large amount of power involved,
transmission normally takes place at high voltage (110 kV or
above). Electricity is usually transmitted over long distance
through overhead power transmission lines. Underground power
transmission is used only in densely populated areas due to its
high cost of installation and maintenance, and because the high
reactive
power produces large charging currents and difficulties in
voltage management.
A power transmission system is sometimes referred
to colloquially as a "grid"; however, for reasons of economy, the
network is not a mathematical grid.
Redundant
paths and lines are provided so that power can be routed from any
power plant to any load center, through a variety of routes, based
on the economics of the transmission path and the cost of power.
Much analysis is done by transmission companies to determine the
maximum reliable capacity of each line, which, due to system
stability considerations, may be less than the physical or thermal
limit of the line. Deregulation
of electricity companies in many countries has led to renewed
interest in reliable economic design of transmission networks.
However, in some places the gaming of a deregulated energy system
has led to disaster, such as that which occurred during the
California electricity crisis of 2000 and 2001.
AC power transmission
AC power transmission is the transmission of electric power by alternating current. Usually transmission lines use three phase AC current. Single phase AC current is sometimes used in a railway electrification system. In urban areas, trains may be powered by DC at 600 volts or so.Overhead conductors are not covered by
insulation. The conductor material is nearly always an aluminum
alloy, made into several strands and possibly reinforced with steel
strands. Conductors are a commodity supplied by several companies
worldwide. Improved conductor material and shapes are regularly
used to allow increased capacity and modernize transmission
circuits. Conductor sizes in overhead transmission work range in
size from #6 American
wire gauge (about 12 square millimetres) to 1,590,000 circular
mils area (about 750 square millimetres), with varying resistance
and current-carrying capacity. Thicker wires would lead to a
relatively small increase in capacity due to the skin effect,
that causes most of the current to flow close to the surface of the
wire.
Today, transmission-level voltages are usually
considered to be 110 kV and above. Lower voltages such as 66 kV and
33 kV are usually considered sub-transmission voltages but are
occasionally used on long lines with light loads. Voltages less
than 33 kV are usually used for distribution.
Voltages above 230 kV are considered extra
high voltage and require different designs compared to
equipment used at lower voltages.
Overhead transmission lines are uninsulated wire,
so design of these lines requires minimum clearances to be observed
to maintain safety.
History
In the early days of commercial use of electric power, transmission of electric power at the same voltage as used by lighting and mechanical loads restricted the distance between generating plant and consumers. Originally generation was with direct current, which could not easily be increased in voltage for long-distance transmission. Different classes of loads, for example, lighting, fixed motors, and traction (railway) systems, required different voltages and so used different generators and circuits.At an AIEE meeting on
May 16,
1888, Nikola Tesla
delivered a lecture entitled
A New System of Alternating Current Motors and Transformers,
describing the equipment which allowed efficient generation and use
of alternating
currents. Tesla's disclosures, in the form of patents, lectures
and technical articles, are useful for understanding the history of
the modern system of power transmission. Ownership of the rights to
the Tesla patents was a key commercial advantage to the
Westinghouse Company in offering a complete alternating current
power system for both lighting and power.
The so-called "universal system" used
transformers both to couple generators to high-voltage transmission
lines, and to connect transmission to local distribution circuits.
By a suitable choice of utility
frequency, both lighting and motor loads could be served.
Rotary
converters and later mercury-arc
valves and other rectifier equipment allowed DC load to be
served by local conversion where needed. Even generating stations
and loads using different frequencies could also be interconnected
using rotary converters. By using common generating plants for
every type of load, important economies
of scale were achieved, lower overall capital investment was
required, load factor
on each plant was increased allowing for higher efficiency,
allowing for a lower cost of energy to the consumer and increased
overall use of electric power.
By allowing multiple generating plants to be
interconnected over a wide area, electricity production cost was
reduced. The most efficient available plants could be used to
supply the varying loads during the day. Reliability was improved
and capital investment cost was reduced, since stand-by generating
capacity could be shared over many more customers and a wider
geographic area. Remote and low-cost sources of energy, such as
hydroelectric
power or mine-mouth coal, could be exploited to lower energy
production cost.
The first transmission of three-phase alternating
current using high voltage took place in 1891 during the
international electricity exhibition in Frankfurt. A 25
kV transmission line, approximately 175 kilometers long, connected
Lauffen on the Neckar and
Frankfurt.
Initially transmission lines were supported by
porcelain pin-and-sleeve insulators
similar to those used for telegraphs and
telephone lines.
However, these had a practical limit of 40 kV. In 1907, the invention of
the disc insulator by Harold W.
Buck of the
Niagara Falls Power Corporation and Edward M.
Hewlett of General
Electric allowed practical insulators of any length to be
constructed for higher voltages. The first large scale
hydroelectric generators in the USA were installed at Niagara
Falls and provided electricity to Buffalo,
New York via power transmission lines. A statue of Tesla stands
at Niagara Falls today in tribute to his contributions.
Voltages used for electric power transmission
increased throughout the 20th century. By 1914 fifty-five
transmission systems operating at more than 70,000 V were in
service, the highest voltage then used was 150,000 volts. The first
three-phase alternating current power transmission at 110 kV took
place in 1912 between Lauchhammer and
Riesa,
Germany. On
April 17, 1929 the first 220 kV line in Germany was
completed, running from Brauweiler near
Cologne,
over Kelsterbach
near Frankfurt, Rheinau
near Mannheim, Ludwigsburg-Hoheneck
near Austria. The masts
of this line were designed for eventual upgrade to 380 kV. However
the first transmission at 380 kV in Germany was on October 5, 1957
between the substations in Rommerskirchen
and Ludwigsburg-Hoheneck. In 1967 the first extra-high-voltage
transmission at 735 kV took place on a Hydro-Québec
transmission line. In 1982 the first transmission at 1200 kV was in
the Soviet
Union.
The rapid industrialization in the 20th century
made electrical transmission lines and grids a critical part of the
economic infrastructure in most industrialized nations.
Interconnection of local generation plants and small distribution
networks was greatly spurred by the requirements of World War
I, where large electrical generating plants were built by
governments to provide power to munitions factories; later these
plants were connected to supply civil load through long-distance
transmission.
Small municipal electrical utilities did not
necessarily desire to reduce the cost of each unit of electricity
sold; to some extent, especially during the period 1880-1890,
electrical lighting was considered a luxury product and electric
power was not substituted for steam power. Engineers such as
Samuel
Insull in the United States and
Sebastian Z. De Ferranti in the United Kingdom were
instrumental in overcoming technical, economic, regulatory and
political difficulties in development of long-distance electric
power transmission. By introduction of electric power transmission
networks, in the city of London the cost of a kilowatthour was
reduced to one-third in a ten-year period.
In 1926 electrical networks in the United Kingdom
began to be interconnected in the National
Grid, initially operating at 132,000 volts.
Bulk power transmission
Engineers design transmission networks to transport the energy as efficiently as feasible, while at the same time taking into account economic factors, network safety and redundancy. These networks use components such as power lines, cables, circuit breakers, switches and transformers.Transmission efficiency is improved by increasing
the voltage using a step-up transformer, which reduces
the current in the conductors, while keeping the power transmitted
nearly equal to the power input. The reduced current flowing
through the conductor reduces the losses in the conductor and
since, according to Joule's Law,
the losses are proportional to the square of the current, halving
the current makes the transmission loss one quarter the original
value.
A transmission grid is a network of power
stations, transmission
circuits, and substations. Energy is usually transmitted within
the grid with three-phase
AC.
DC systems
require relatively costly conversion equipment which may be
economically justified for particular projects. Single phase AC is
used only for distribution to end users since it is not usable for
large polyphase induction
motors. In the 19th century two-phase transmission was used,
but required either three wires with unequal currents or four
wires. Higher order phase systems require more than three wires,
but deliver marginal benefits.
The capital cost of electric power stations is so
high, and electric demand is so variable, that it is often cheaper
to import some portion of the variable load than to generate it
locally. Because nearby loads are often correlated (hot weather in
the Southwest portion of the United States might cause many people
there to turn on their air conditioners), imported electricity must
often come from far away. Because of the economics of load
balancing, transmission grids now span across countries and even
large portions of continents. The web of
interconnections between power producers and consumers ensures
that power can flow even if a few links are inoperative.
The unvarying (or slowly varying over many hours)
portion of the electric demand is known as the "base
load", and is generally served best by large facilities (and
therefore efficient due to economies of scale) with low variable
costs for fuel and operations, i.e. nuclear, coal, hydro.
Renewables such as solar, wind, ocean/tidal, etc. are not
considered "base load" but can still add power to the grid.
Smaller- and higher-cost sources such as combined cycle or
combustion turbine plants that run on natural gas are then added as
needed.
Long-distance transmission of electricity
(thousands of miles) is cheap and efficient, with costs of US$
0.005 to 0.02 per kilowatt-hour (compared to annual averaged large
producer costs of US$ 0.01 to US$ 0.025 per kilowatt-hour, retail
rates upwards of US$ 0.10 per kilowatt-hour, and multiples of
retail for instantaneous suppliers at unpredicted highest demand
moments). Thus distant suppliers can be cheaper than local sources
(e.g. New York City buys a lot of electricity from Canada).
Multiple local sources (even if more expensive and infrequently
used) can make the transmission grid more fault tolerant to weather
and other disasters that can disconnect distant suppliers.
Long distance transmission allows remote
renewable energy resources to be used to displace fossil fuel
consumption. Hydro and wind sources can't be moved closer to high
population cities, and solar costs are lowest in remote areas where
local power needs are the least. Connection costs alone can
determine whether any particular renewable alternative is
economically sensible. Costs can be prohibitive for transmission
lines.
Grid input
At the generating plants the energy is produced at a relatively low voltage of up to 30 kV (Grigsby, 2001, p. 4-4), then stepped up by the power station transformer to a higher voltage (115 kV to 765 kV AC, ± 250-500 kV DC, varying by country) for transmission over long distances to grid exit points (substations).Losses
Transmitting electricity at high voltage reduces the fraction of energy lost to Joule heating. For a given amount of power, a higher voltage reduces the current and thus the resistive losses in the conductor. For example, raising the voltage by a factor of 10 reduces the current by a corresponding factor of 10 and therefore the I^2R\,\! losses by a factor of 100, provided the same sized conductors are used in both cases. Even if the conductor size is reduced x10 to match the lower current the I^2R\,\! losses are still reduced x10. Long distance transmission is typically done with overhead lines at voltages of 115 to 1,200 kV. However, at extremely high voltages, more than 2,000 kV between conductor and ground, corona discharge losses are so large that they can offset the lower resistance loss in the line conductors.Transmission and distribution losses in the USA
were estimated at 7.2% in 1995
http://climatetechnology.gov/library/2003/tech-options/tech-options-1-3-2.pdf,
and in the UK at 7.4% in 1998. http://www.powerwatch.org.uk/energy/graham.asp
As of 1980, the longest cost-effective distance
for electricity was 4,000 miles (7,000 km), although all
present transmission lines are considerably shorter. (see
Present Limits of High-Voltage Transmission)
In an alternating current transmission line, the
inductance and
capacitance of the
line conductors can be significant. The currents that flow in these
components of transmission line impedance
constitute reactive
power, which transmits no energy to the load. Reactive current
flow causes extra losses in the transmission circuit. The ratio of
real power (transmitted to the load) to apparent power is the
power
factor. As reactive current increases, the reactive power
increases and the power factor decreases. For systems with low
power factors, losses are higher than for systems with high power
factors. Utilities add capacitor banks and other components
throughout the system — such as phase-shifting
transformers, static
VAR compensators, and
flexible AC transmission systems (FACTS) — to control
reactive power flow for reduction of losses and stabilization of
system voltage.
Electrical
power is always partially lost by transmission. This applies to
short distances such as between components on a printed
circuit board as well as to cross country high voltage lines.
The major component of power loss is due to ohmic losses in the
conductors and is equal to the product of the square of the current
and the resistance
of the wire:
P_ = I^2 R.\,\!
For a system which delivers a power, P, at unity
power factor at a particular voltage, V, the current flowing
through the cables is given by I = \frac. Thus, the power lost in
the lines, P_ = I^2 R = \left(\frac\right)^2 R = \frac.
Therefore, the power lost is proportional to the
resistance and inversely proportional to the square of the voltage.
A higher transmission voltage reduces the current and thus the
power lost during transmission.
In addition, a low resistance is desirable in the
cable. While copper cable could be used, aluminium alloy is preferred
due to its much better conductivity to weight ratio making it
lighter to support, as well as its lower cost. The aluminium is
normally mechanically supported on a steel core.
HVDC
High voltage direct current (HVDC) is used to transmit large amounts of power over long distances or for interconnections between asynchronous grids. When electrical energy is required to be transmitted over very long distances, it can be more economical to transmit using direct current instead of alternating current. For a long transmission line, the value of the smaller losses, and reduced construction cost of a DC line, can offset the additional cost of converter stations at each end of the line. Also, at high AC voltages significant (although economically acceptable) amounts of energy are lost due to corona discharge, the capacitance between phases or, in the case of buried cables, between phases and the soil or water in which the cable is buried.HVDC links are sometimes used to stabilize
against control problems with the AC electricity flow. In other
words, to transmit AC power as AC when needed in either direction
between Seattle and
Boston would
require the (highly challenging) continuous real-time adjustment of
the relative phase of
the two electrical grids. With HVDC instead the interconnection
would: (1) Convert AC in Seattle into HVDC. (2) Use HVDC for the
three thousand miles of cross country transmission. Then (3)
convert the HVDC to locally synchronized AC in Boston, and
optionally in other cooperating cities along the transmission
route. One prominent example of such a transmission line is the
Pacific
DC Intertie located in the Western United
States.
Grid exit
At the substations, transformers are again used to step the voltage down to a lower voltage for distribution to commercial and residential users. This distribution is accomplished with a combination of sub-transmission (33 kV to 115 kV, varying by country and customer requirements) and distribution (3.3 to 25 kV). Finally, at the point of use, the energy is transformed to low voltage (100 to 600 V, varying by country and customer requirements).Limitations
The amount of power that can be sent over a transmission line is limited. The origins of the limits vary depending on the length of the line. For a short line, the heating of conductors due to line losses sets a "thermal" limit. If too much current is drawn, conductors may sag too close to the ground, or conductors and equipment may be damaged by overheating. For intermediate-length lines on the order of 100 km (60 miles), the limit is set by the voltage drop in the line. For longer AC lines, system stability sets the limit to the power that can be transferred. Approximately, the power flowing over an AC line is proportional to the sine of the phase angle between the receiving and transmitting ends. Since this angle varies depending on system loading and generation, it is undesirable for the angle to approach 90 degrees. Very approximately, the allowable product of line length and maximum load is proportional to the square of the system voltage. Series capacitors or phase-shifting transformers are used on long lines to improve stability. High-voltage direct current lines are restricted only by thermal and voltage drop limits, since the phase angle is not material to their operation.Communications
Operators of long transmission lines require reliable communications for control of the power grid and, often, associated generation and distribution facilities. Fault-sensing protection relays at each end of the line must communicate to monitor the flow of power into and out of the protected line section so that faulted conductors or equipment can be quickly de-energized and the balance of the system restored. Protection of the transmission line from short circuits and other faults is usually so critical that common carrier telecommunications are insufficiently reliable. In remote areas a common carrier may not be available at all. Communication systems associated with a transmission project may use: Rarely, and for short distances, a utility will use pilot-wires strung along the transmission line path. Leased circuits from common carriers are not preferred since availability is not under control of the electric power transmission organization.Transmission lines can also be used to carry
data: this is called power-line carrier, or PLC.
PLC signals can be easily received with a radio for the long wave
range.
Optical fibers can be included in the stranded
conductors of a transmission line, in the overhead shield wires.
These cables are known as OPGW or Optical Ground
Wire. Sometimes a standalone cable is used, ADSS or All Dielectric
Self Supporting cable, attached to the transmission line cross
arms.
Some jurisdictions, such as Minnesota,
prohibit energy transmission companies from selling surplus
communication bandwidth or acting as a telecommunications common
carrier. Where the regulatory structure permits, the utility
can sell capacity in extra "dark fibers" to a common carrier,
providing another revenue stream for the line.
Electricity market reform
Some regulators, economists, and many power companies regard electric transmission to be a natural monopoly and there are moves in many countries to separately regulate transmission (see Electricity market).Spain was the first
country to establish a Regional Transmission Organization. In that
country transmission operations and market operations are
controlled by separate companies. The transmission system operator
is Red Eléctrica de España (REE) http://www.ree.es/ingles/i-index_quien.html
and the wholesale electricity market operator is Operador del
Mercado Ibérico de Energía - Polo Español, S.A. (OMEL) http://www.omel.es. Spain's transmission
system is interconnected with those of France, Portugal, and
Morocco.
In the United States and parts of Canada,
electrical transmission companies operate independently of
generation and distribution companies.
Merchant transmission
Merchant transmission is an arrangement where a third party constructs and operates electric transmission lines through the franchise area of an unrelated utility. Advocates of merchant transmission claim that this will create competition to construct the most efficient and lowest cost additions to the transmission grid. Merchant transmission projects typically involve DC lines because it is easier to limit flows to paying customers.The only operating merchant transmission project
in the United
States is the Cross
Sound Cable from Long
Island, New York to New
Haven, Connecticut, although additional projects have been
proposed.
There are five merchant transmission
interconnectors between five states in Australia: the
DirectLink, QNI, MurrayLink and Southern Link between New South
Wales and South Australia and Basslink between
Tasmania and Victoria.
A major barrier to wider adoption of merchant
transmission is the difficulty in identifying who benefits from the
facility so that the beneficiaries will pay the toll. Also, it is
difficult for a merchant transmission line to compete when the
alternative transmission lines are subsidized by other utility
businesses.
Health concerns
Some research has found that exposure to elevated levels of ELF magnetic fields such as those originating from electric power transmission lines may be implicated in a number of adverse health effects. These include, but are not limited to, childhood leukemia , adult leukemia, breast cancer, neurodegenerative diseases (such as amyotrophic lateral sclerosis), Miscarriage, and clinical depression. Although there seems to be a small statistical correlation between various diseases and living near power lines, the physical mechanism is not clear. One proposed mechanism is that the electric fields around power lines attract aerosol pollutants.One possible response to the potential dangers of
overhead power lines is to place them underground. According to the
British Stakeholder Advisory Group on ELF EMFs, the cost of burying
cables at transmission voltages is around GBP 10M/km, compared to
GBP 0.5-1M/km for overhead lines.
Underground cables eliminate the electric field
and reduce the width over which the magnetic field is elevated.
However, in reality, protection from the dangers of electromagnetic
(EM) fields is seldom the driving concern when burying power
lines.
The strongest evidence linking EMF to cancer was
fabricated. Most people, when quizzed, have heard of the link
between EMF's and cancer, but relatively few people have heard of
the fabricated data leaving a public perception that power lines
are far more dangerous than they are.http://www.sciencemag.org/cgi/content/summary/285/5424/23b
Indeed, the UN World
Health Organization has concluded "...a cause-and-effect link
between ELF field exposure and cancer has not been
confirmed."http://www.who.int/mediacentre/factsheets/fs205/en/
Special transmission
Grids for railways
In some countries where electric trains run on low frequency AC (e.g. 16.7 Hz and 25 Hz) power, there are separate single phase traction power networks operated by the railways. These grids are fed by separate generators in some traction powerstations or by traction current converter plants from the public three phase AC network.Radio frequency power transmission
Some radio broadcasters use specialized transmission lines to carry the output of high-power transmitters to the antenna.Superconducting cables
High-temperature superconductors promise to revolutionize power distribution by providing lossless transmission of electrical power. The development of superconductors with transition temperatures higher than the boiling point of liquid nitrogen has made the concept of superconducting power lines commercially feasible, at least for high-load applications. It has been estimated that the waste would be halved using this method, since the necessary refrigeration equipment would consume about half the power saved by the elimination of the majority of resistive losses. Such cables are particularly suited to high load density areas such as the business district of large cities, where purchase of a wayleave for cables would be very costly. http://www.futureenergies.com/print.php?sid=237Single wire earth return
Single wire earth return (SWER) or single wire ground return is a single-wire transmission line for supplying single-phase electrical power for a electrical grid to remote areas at low cost. It is principally used for rural electrification, but also finds use for larger isolated loads such as water pumps, and light rail. Single wire earth return is also used for HVDC over submarine power cables.Wireless power transmission
Every radio transmitter emits power wirelessly. Both Nikola Tesla and Hidetsugu Yagi attempted to devise systems for large scale wireless power transmission. Tesla claimed to have succeeded. Yagi also proposed a similar concept, but the engineering problems proved to be more onerous than conventional systems. His work, however, led to the invention of the Yagi antenna.Another form of wireless power transmission has
been studied for transmission of power from solar
power satellites to the earth. A high power array of microwave transmitters would
beam power to a rectenna. Major engineering and
economic challenges face any solar power satellite project.
Another form is the operation of a crystal
radio is powered by the radio station it is tuned to, however
the energetic efficiency is extremely low. Small scale wireless
power was demonstrated as early as 1831 by Michael
Faraday and by 1888 Heinrich
Rudolf Hertz had proven that natural radio waves exist and can
be captured.
Records
- Highest transmission voltage (AC): 1,150 kV on Powerline Ekibastuz-Kokshetau (Kazakhstan)
- Highest transmission voltage (DC): +/-600 kV on HVDC Itaipu (Brazil)
- Highest pylons: Yangtze River Crossing (height: )
- Longest power line: Inga-Shaba (length: )
- Longest span of power line: at Ameralik Span
- Longest submarine cables:
- NorNed, North Sea - (length of submarine/underground cable: )
- Basslink, Bass Strait - (length of submarine/underground cable: , total length: )
- Baltic-Cable, Baltic Sea - (length of submarine/underground cable: , total length: )
See also
Notes
Further reading
- Grigsby, L. L., et al. The Electric Power Engineering Handbook. USA: CRC Press. (2001). ISBN 0-8493-8578-4
- Thomas P. Hughes, Networks of Power: Electrification in Western Society 1880-1930, The Johns Hopkins University Press,Baltimore 1983 ISBN 0-8018-2873-2, an excellent overview of development during the first 50 years of commercial electric power
- Westinghouse Electric Corporation, "Electric power transmission patents; Tesla polyphase system". (Transmission of power; polyphase system; Tesla patents)
External links
- Japan: World's First In-Grid High-Temperature Superconducting Power Cable System
- A Power Grid for the Hydrogen Economy: Overview/A Continental SuperGrid
- Global Energy Network Institute (GENI) - The GENI Initiative focuses on linking renewable energy resources around the world using international electricity transmission.
- Union for the Co-ordination of Transmission of Electricity (UCTE), the association of transmission system operators in continental Europe, running one of the two largest power transmission systems in the world
- Non-Ionizing Radiation, Part 1: Static and Extremely Low-Frequency (ELF) Electric and Magnetic Fields (2002) by the IARC -- Link Broken.
- Trustworthy Cyber Infrastructure for the Power Grid (TCIP) - The TCIP group at the University of Illinois at Urbana-Champaign has developed applets to illustrate important concepts in mathematics and the science of electricity and the power grid.
intertie in Bulgarian: Електрически
далекопровод
intertie in Czech: Přenosová soustava
intertie in German: Stromnetz
intertie in Spanish: Red de transporte de
energía eléctrica
intertie in Persian: انتقال انرژی الکتریکی
intertie in French: Réseau électrique
intertie in Italian: Trasmissione di energia
elettrica
intertie in Lithuanian: Elektros perdavimo
linija
intertie in Hungarian: Átviteli hálózat
intertie in Dutch: Hoogspanningsnet
intertie in Japanese: 送電
intertie in Norwegian: Fordelingsnett
intertie in Portuguese: Transmissão de energia
elétrica
intertie in Russian: Линия электропередачи
intertie in Simple English: Electric power
transmission
intertie in Finnish: Sähköverkko
intertie in Swedish: Kraftledning
intertie in Chinese: 輸電系統